It applies to large-current DC power supply in the electrolytics industry and metal industry and can be used as power supply for aluminum, magnesium, zinc, manganese and lead electrolysis, DC electric arc furnace melting, salt electrolysis, water electrolysis, graphitization furnace and silicon carbide and the power supply of similar load nature.

 

Structure overview:

The control cabinet is of GGD closed structure and opposed access door at the front and back for operation and maintenance. The gauge, control switch and potentiometer are installed front door plank of the cabinet; the signal light is installed on the top panel in the front of the cabinet and the entrance hole is set at the bottom of the cabinet for user connection. See Figure (II) for its appearance and installation dimensions.

Model

KHS-55000A/190V

Efficiency

≥98.7%

Input Voltage

AC10KV

Rated Voltage

DC190V

Input Current

AC728A

Rated Current

DC55000A

Range of Regulation

 

On-load Voltage Regulation+ Thyristor Phase Controlled Voltage Regulation: 0%-100% Udn

Notes forOrder

 

Input Voltage

AC380V-330KV

Optional


Frequency

40-60Hz

Optional


Current Regalation


Optional


Voltage Regulation


Optional


Rated Current


Optional


Rated Voltage


Optional


Cooling Mothed

Water,Air,natural or Forced

Draft Cooling

Optional

The High Current Rectifiers listed on this website is customized, just for your reference. If you have any specific demands,please tell us the parameters in details. We’ll be more than happy to work with you to meet your exact requirements.

The main parameters of our Thyristor / Diode High Current Rectifiers for Industrial Applications:

A)Voltage Specification:  5V - 3000V

B)  Current Specification:  300A - 240000A

C)  Output Current Adjusting Range: 0 - 1000A


Digest of High Current Rectifier(HCR)technical documents.

Part nine of User Manual


IV. Installation and Debugging

1. Installation

1.1 The control cabinet must be installed indoors without special foundation. For easy maintenance, the cabinet shall be no less than 1m from the wall in the back, no less than 2m in the front and no less than 0.5m in the side.

1.2 Pay attention to the following after unpacking and before installation of the control cabinet:

1.3 Do not keep outdoors after unpacking.

1.4 Check the damageable parts in the cabinet and replace if damaged.

1.5 Check whether the printed board and other welding spots in the control cabinet fall off and are insufficient and whether the elements are loose and fall off. Check carefully with a multimeter before power-on.

2. Debugging

2.1 Connect the major loop and the control loop diagram according to the system diagram, check circuit connection without error, insert the control loop fuse, power on the control loop and conduct the following debugging:

2.2 Turn the control cabinet air switch to "Run", connect the power supply of the signal detection circuit and simulate the rectifier failure. The audible and visual alarm shall issue normal alarm sound. Check the working conditions of each relay and signal light.

3. Trigger control circuit debugging

Observe the phase shift of six-way pulse with oscilloscope. The pulse phase shift range shall be 0~150°.

4. Control protection circuit setting

4.1 Inlet water pressure setting: with the lower limit of 0.03MPa. When the water pressure is below this value, the signal system shall give a reliable alarm.

4.2 Outlet water temperature setting: with the upper limit of 50℃. When the water temperature is above this value, the signal system shall give a reliable alarm.

4.3 Current overload setting: the current signal is taken from the user's DC sensor with the setting value of 1.1 times the rated current value (or determined by the user depending on circumstances). When the rectified current exceeds this value, the signal system shall give a reliable alarm.

4.4 Feedback signal loss setting: the current signal is taken from the user's DC sensor with the setting value of 0.5V (or determined by the user depending on circumstances). When the rectified current is below this value, the signal system shall give a reliable alarm.

Before major loop power-on, observe whether pulse of the thyristor pulse distributor in the rectifier cabinet is normal and verify the phase relation between the major loop and the trigger circuit.


 

High Current Rectifier(HRC)KHS-55000A/190V Structure Feature & Advantages

▲ Adopted cophase counter parallel connection Rectification,wihich can increase the power factor and reduce power loss

▲ Three-phase bridge rectification,which has the characteristics of reliability,stability,and low losses

▲ Adopted aluminum frame and glass antimagnetic cabinet, which suit for monitor and maintenance

▲ Power is scalable

▲ Can be maintained with electricity.

▲ With Low noise 

▲ Easy to operate 

▲ Superiority of Ture Rdundancy technique

▲Over / low Voltage protection    

▲Over / low current protection   

▲Over / lack water protection        

▲Over temperature protection

▲Fast fuse protection      

▲Phase protection  

 

Our products of High Current Rectifier (HRC) are customized according to clients’s parameters.They are used in variety of applications as follows:

1.Plating: Chrome, Zine, Nickel, Copper, Gold, Silver

2.Metal smelting: Aluminum, Copper,  Zine, Lead, Manganese, Magnesium, etc.

3.Ionic membrane: Electrolysis of salt, etc

4.Silicon carbide smelting & Graphitization furnace

5.Experimental power supply

6.Copper foil, aluminum foil special power supply

7.Electrochemical: Chlor-alkali, etc

8.Electrolysis: Copper, Zine, Tin, Lead, Aluminum foil, Copper foil

The expert teams with 20 years experience can supply equipment design,manufacture, upgrading and after sales service. It’s quality management system meets the requirement of the ISO9001:2008 standard. The Technical level of main equpment is ten years ahead in China,and the control system is twenty years ahead at home and abroad.

We service with pride and care and give you a best solution.

 Packing Details:In iron sheet case with waterproof and anti collision treatment

Delivery Details: 1-3 months, depending on your technical parameters

Please give us the follows technical information before order:

1  A.C. INPUT

• A.C: rated voltage

• Phases

• Frequency

2  D.C. OUTPUT

• Rated D.C. voltage

• Rated D.C. current

• D.C. voltage fine control range (thyristors)

• D.C: current control range

• Accuracy of current fine control

• Pulse number

• Ripple

1. Within the first year, if you need any spare parts for replacement, we can provide to you without paid. And we will offer lifelong technical support and service.

2. Within the first year, if you need any spare parts for replacement, we can provide to you without paid. And we will offer lifelong technical support and service.

 

1.Q:Are you a factory or trading company?
A: We are a factory.

 

2. Q: Where is your factory? How can I visit there?

A: Our factory is located in Xi’an, middle part of China, about an hour bus ride from Xi’an Xianyang Airport, which in the starting point of Ancient Silk Road.Welcome to visit us.

 

3. Q:When can I get the price?

A:Usually we quote within 24 hours after we get your inquiry.


Total0bar [View All]  Related Comments
 
More>other products

[ ProductsSearch ]  [ Send Fav ]  [ Share ]  [ Print ]  [ Send Report ]  [ Close ]

 
Home | Products | Suppliers | News | Tradeshow | Sitemap | Message | RSS Feed